SUMMARY OF AS4775:2007 - EMERGENCY SHOWER & EYE WASH EQUIPMENT
- Flushing fluid shall be tepid (check with medical advisor for optimum temperature)
- Equipment shall be tested weekly to verify proper operation and inspected annually to assure conformance with AS4775:2007 requirements
- All emergency equipment needs to be connected to a supply that will allow for a minimum of 15 minutes of operation
- All emergency equipment is required to be third party certified for compliance to the AS4775:2007 Standard
- Combination unit components shall be capable of operationg simultaneously
Eye & Eye Face Washes:
- Eye wash - 1.5 litres per minute
- Eye/face wash - 11.4 litres per minute
- Nozzles protected from airborne contaminates
- Provide flushing fluid to both eyes simultaneously
- At a velocity low enough to be non-injurious
- Simple operation - "off to on" in one second or less
- Height from standing surface 8.8mm to 1143mm
- Minimum operating pressure - 210kpa
- Hands-free operation once activated
Showers:
- Minimum flow of 75.7 litres per minute
- Simple operation 0 "off to on" in one second or less
- Height from standing surface 2083mm to 2438mm
- Pattern: 508mm diameter at 1524mm above standing surface
- Centre of spray located 406mm from any obstruction
- Minimum supply pipe size - 25mm
- Hands free operation once activated